Conductor                                                                         Cable
Cross section Number of strands Max. diameter of strands Max. diameter Max. conductor resistance Insulation wall thickness Min. external diameter Max. external diameter Standard delivery length
mm²   mm mm Ω/km@ 20°C mm mm mm m
Thin Wall
10 50 0.52 4.50 3.03 0.48 5.40 5.80 1 300
16 78 0.52 5.50 1.93 0.52 6.50 7.00 1 000
20 96 0.52 6.10 1.59 0.52 7.30 7.80 750
25 120 0.52 7.00 1.24 0.52 8.20 8.70 500
30 144 0.52 7.40 1.08 0.64 9.00 9.60 450
35 168 0.52 8.30 0.878 0.64 9.80 10.40 350
40 192 0.52 8.90 0.788 0.72 10.40 11.10 300
50 240 0.52 9.80 0.613 0.72 11.50 12.20 550
60 288 0.52 10.50 0.525 0.80 12.50 13.30 250
70 344 0.52 11.60 0.432 0.80 13.50 14.40 200
85 420 0.52 13.20 0.365 0.90 14.40 15.30 500
Thick Wall
35 168 0.52 8.50 0.878 1.04 9.80 10.40 350
40 192 0.52 9.60 0.788 1.12 11.20 12.40 300
60 288 0.52 11.60 0.525 1.20 13.40 14.60 600
 