R8481A-T500 
 ACOLAN® COPPER
                                Applications
- 10 Gigabit high speed data transmission cables are designed for horizontal cable distribution local computer networks.
- These cables allow the use of the protocol supported by the class FA for the 10 GBASE-T applications.
- They are characterized of up to 1500 MHz.
- They are compatibles with PoE & PoE+, UPoE & 4PPoE (PoE++) applications.
See our White Paper on installation conditions on www.acome.com also available on demand.
General characteristics
| 
 | Solid annealed red copper wire, AWG 22 | 
| 
 | Cable assembly in Twisted Pairs | 
| 
 | Pet/Alu foil around each pair | 
| 
 | 4 pairs screening assembly | 
| 
 | Tinned copper braid | 
| 
 | LSOH-FR : Low Smoke « Zero » Halogen – Flame Retardant | 
| Designation ACOLAN FIREPROTECT | Ref. | Colour | Diameter | Weight | Superior calorific capacity (PCS) | Max pulling tension | |
| mm | Kg/km | MJ/km | KWh/m | N | |||
| 1500 SF-S 4P LSOH-FR | R8481A | Yellow | 7.70 | 57 | 521 | 0,145 | 125 | 
| 1500 SFD-S 4P LSOH-FR | R8482A | Yellow | 7.90 x 16.00 | 124 | 1169 | 0,325 | 250 | 
| Caractéristiques | Valeurs | |
| Bending radius | Dynamics (installation) | ≥ 70 mm | 
| Static (installed) | ≥ 35 mm | |
| Temperature range | In service | - 20°C at+ 60°C | 
| At the installation | 0°C at+ 50°C | |
| Transport and storage | 0°C at+ 50°C | |
Electrical characteristics at 20°C (68°F)
| Caractéristiques | Valeurs | ||
| Complete conductor resistance | ≤ 120 Ω / km | ||
| Resistance unbalance | ≤ 2 % | ||
| Dielectric strengh | Continuous current | 1kV during 1 minute = no breakdown | |
| Insulation resistance | (500 V) | ≥ 5000 MΩ . km | |
| Capacitance unbalance | Real-ground | ≤ 1200 pF / km | |
| Characteristic impedance | at 100 MHz | 100 ± 5 Ω | |
| Velocity | nominal | 78% | |
| Coupling attenuation | ≥ 85 dB | TYPE 1b | |
| Transfert impedance | at 1 MHz | ≤ 10 mΩ / m | GRADE 1 | 
| at 10 MHz | ≤ 10 mΩ / m | ||
| at 30 MHz | ≤ 20 mΩ / m | ||
| at 100 MHz | ≤ 30 mΩ / m | ||
| Segregation classification acc. to EN 50174-2 | ‘’d’’ | ||
| Frequency (MHz) | 4 | 10 | 20 | 62.5 | 100 | 250 | 300 | 600 | 1000 | 1200 | 1500** | |
| Attenuation. (dB/100m) | Typical value | 3.4 | 5.2 | 7.4 | 13.4 | 16.8 | 27.4 | 30 | 43.0 | 57.8 | 64.0 | 73.0 | 
| Imposition (max)* | 3.7 | 5.8 | 8.2 | 14.6 | 18.5 | 29.7 | 32.7 | 47.1 | 61.9 | - | - | |
| Next (dB) | Typical value | 100 | 100 | 100 | 100 | 100 | 92 | 90 | 87 | 85 | 83 | 80 | 
| Imposition (min)* | 75 | 75 | 75 | 75 | 73 | 67 | 66 | 61 | 58 | - | - | |
| PS Next (dB) | Typical value | 97 | 97 | 97 | 97 | 97 | 89 | 87 | 84 | 82 | 80 | 77 | 
| Imposition (min)* | 75 | 75 | 75 | 73 | 70 | 64 | 63 | 58 | 55 | - | ||
| ELFEXT (dB/100 m) | Typical value | 90 | 90 | 85 | 84 | 80 | 72 | 69 | 61 | 56 | 53 | 50 | 
| Imposition (min)* | 78 | 74 | 68 | 58 | 54 | 46 | 44 | 38 | 34 | - | - | |
| PS ELFEXT (dB/100 m) | Typical value | 87 | 87 | 82 | 81 | 77 | 69 | 66 | 58 | 53 | 50 | 47 | 
| Imposition (min)* | 75 | 71 | 65 | 55 | 51 | 43 | 41 | 35 | 31 | - | - | |
| Return Loss (dB) | Typical value | 26 | 28 | 28 | 28 | 26 | 24 | 22 | 19 | 18 | 18 | 17 | 
| Imposition (min)* | 23 | 25 | 25 | 21.5 | 20.1 | 17.3 | 17.3 | 17.3 | 15.1 | - | - | 
* Category 7a according IEC 61 156-5 Ed. 2nd
** For information only
Norms and standards
Applications
IEEE 802.3 :10Base-T; 100Base-TX;1000Base-T; 2,5GBase-T ;  5GBase-T ; 10GBase –T
IEEE 802.3 af (PoE) / 802.3 at (PoE+) / 802.3 bt (4PPoE 90W)
IEEE 802.5 /  FDDI / ATM / RNIS
Cable
IEC 61156-5 ed.2 /  EN 50288-9-1
Cabling system standard
ISO/IEC 11801 2nd ed. / EN 50173-1
Cabling system installation standards
EN 50174
Directive / Regulation
RoHS 2011/65/UE
REACH 1907/2006/EC
Europe
| Type | Euroclass | Standards | Declaration of performance | |
| 4P | Dca-s2,d2,a1 | IEC 60332-1, EN 50399, IEC 60754-2 | 20SFTP018 | |
| 2x4P | 20SFTP019 | |||
Outside Europe
| No flame propagation | IEC 60332-1 / EN 60332-1 | 
| Low smoke opacity | IEC 61034-2 / EN 61034-2 | 
| Low gas corrosivity | IEC 60754-2 / EN 60754-2 | 
| Low toxicity | IEC 60754-1 / EN 60754-1 | 
Recommendations
| Type | References | Individual | Expedition | ||||
| Type | Weight | EAN code | Quantity | Weight | EAN code | ||
| 4P LSOH-FR | R8481A-T500 | Drum KT of 500 m | 31 kg | 3700223642267 | 12 drums | 389 kg | 3700223642274 | 
| R8481A-T1000 | Drum XL of 1000 m | 62 kg | 3700223644384 | 4 drums | 262 kg | 3700223644377 | |
| 2 x 4P LSOH-FR | R8482A-T500 | Drum XL of 500 m | 67 kg | 3700223644278 | 4 drums | 282 kg | 3700223644285 | 
 
    
       
    
                        