R7435B-T500
ACOLAN COPPER
Applications
- High speed data transmission cables are designed for horizontal cable distribution local computer networks.
- Protected by a black UV resistant LSOH-FR sheath for outdoor use.
- These cables are permitted the protocol supported by the class D.
- They are characterized of up to 200 MHz.
- They are compatibles with PoE & PoE+, UPoE applications.
General characteristics
|
Solid annealed red copper wire, AWG 24
|
|
Cable assembly in Twisted Pairs |
3. Cable assembly |
4 pairs assembly |
4. Screen |
Pet/Alu foil and tinned copper braid (80%) |
5. External sheath |
LSOH-FR UV stabilize |
Designation ACOLANâ |
Ref. |
Colour |
Diameter |
Weight |
Superior calorificcapacity (PCS) |
Max pulling tension |
|
mm |
Kg/km |
MJ/km |
KWh/m |
N |
|||
200 SFU-S 4P LSOH-FR IN/OUT |
R7435B |
Black |
6.80 to 7.10 |
69 |
665 |
0,185 |
500 |
Characteristics |
Values |
|
Bending radius |
Dynamic (installation) |
≥ 60 mm |
Static (installed) |
≥ 30 mm |
|
Temperature range |
In service |
- 40°C at + 75°C |
At the installation |
- 20°C at + 60°C |
|
Transport and storage |
- 40°C at + 75°C |
|
Waterproofness | Minimum | IP67 |
Characteristics |
Values |
||
Complete conductor resistance |
Any conductor Shield |
≤ 95 Ω / km ≤ 10.50 Ω / km |
|
Resistance unbalance |
|
≤ 2 % |
|
Dielectric strength |
Continuous current |
1.5 kV during 1 minute = no breakdown 5 kV DC during 3 seconds = no breakdown |
|
Insulation resistance |
(500 V) |
≥ 5000 MΩ . km |
|
Capacitance unbalance |
Real-ground |
≤ 1600 pF / km |
|
Characteristic impedance |
at 100 MHz |
100 ± 5 Ω |
|
Velocity |
nominal |
66 % |
|
Coupling attenuation |
|
≥ 85 dB |
TYPE 1 |
Transfert impedance
|
at 1 MHz | ≤ 10 MΩ / m | GRADE 1 |
at 10 MHz | ≤ 10 MΩ / m | ||
at 30 MHz |
≤ 20 MΩ / m | ||
at 100 MHz | ≤ 30 MΩ / m | ||
Segregation classification acc. EN 50174-2 | "d" |
Transmission characteristics at 20° C
Frequency (MHz) |
4 | 10 | 20 | 62.5 | 100 | 155** | 200** | |
Attenuation (dB/100m) | Typical value | 3.8 | 6 | 8.5 | 15.2 | 19.5 | 25 | 28 |
Imposition (max)* | 4.1 | 6.5 | 9.3 | 17 | 22 | - | - | |
Next (dB) | Typical value | 63 | 57 | 52 | 45 | 42 | 39 | 37 |
Imposition (min)* | 56.3 | 50.3 | 45.8 | 38.4 | 35.3 | - | - | |
ACR (dB) | Typical value | 59.2 | 51 | 43.5 | 29.8 | 22.5 | 14 | 9 |
Imposition (min)* | 52.2 | 43.8 | 36.5 | 21.4 | 13.3 | - | - | |
PS Next (dB) | Typical value | 60 | 54 | 49 | 42 | 39 | 36 | 34 |
Imposition (min)* | 53.3 | 47.3 | 42.8 | 35.4 | 32.3 | - | - | |
ELFEXT (dB/100 m) | Typical value | 63 | 55 | 48 | 39 | 35 | 31 | 29 |
Imposition (min)* | 52 | 44 | 38 | 28 | 24 | - | - | |
PS ELFEXT (dB/100 m) | Typical value | 60 | 52 | 45 | 36 | 32 | 28 | 26 |
Imposition (min)* | 49 | 41 | 35 | 25 | 21 | - | - | |
Return Loss (dB) | Typical value | 25 | 25 | 25 | 23.8 | 23 | 22 | 21 |
Imposition (min)* | 23 | 25 | 25 | 21.5 | 20.1 | - | - |
Norms and standards
Application
IEEE 802.3: 10Base-T, 100Base-T ;1000Base-T ;
IEEE 802.3 af (PoE) / 802.3 at (PoE+)
IEEE 802.5 / FDDI / ATM / RNIS
Cables
IEC 61156-5 / EN 50288-2-1
Cabling system standard
ISO/IEC 11801 2nd ed. / EN 50173-1 / TIA-568.2-D
Cabling system installation standards
EN 50174
Directive / Regulation
RoHS 2011/65/UE
REACH 1907/2006/EC
Europe
Type |
Euroclass |
Standards |
Declaration of performance |
|
4P |
Eca |
IEC 60332-1 |
Outside Europe
No flame propagation |
IEC 60332-1 / EN 60332-1 |
Low smoke opacity |
IEC 61034-2 / EN 61034-2 |
Low gas corrosivity |
IEC 60754-2 / EN 60754-2 |
Low toxicity |
IEC 60754-1 / EN 60754-1 |
Recommendations
Type |
References |
Individual |
Expedition |
||||
Type |
Weight |
EAN code |
Quantity |
Weight |
EAN code |
||
4P |
R7435B-T500 |
Drum KT of 500 m |
37 kg |
3700223679553 |
18 drums |
681 kg |
3700223679546 |
R7435B-T1000 | Drum XC of 1000 m | 74 kg | 3700223679539 | 6 drums | 457 kg | 3700223679522 |